Hager VME02SPD Consumer Unit Surge Protection Kit Type 2
Hager VME02SPD Consumer Unit Surge Protection Kit Type 2
A Surge protection kit specifically developed for Hager Consumer units. Developed to ensure optimal performance of SPD technology within the residential single phase consumer units. SPD is CT2 type to ensure compatibility with all common UK Earthing arrangements e.g. TN-C-S (PME), TN-S and TT earthing arrangements. This is an IEC Type 2 / class II SPD for single phase power supply networks.
This SPD kit fits within the standard consumer unit. Line and Neutral connections are via a 2 pole copper busbar from the SPD to the supply side of the main incoming device terminated within the top of the devices bi-connect, the earth cable will be terminated within the main earth bar within the consumer unit, and terminated in either the left hand or right hand earth terminal at the top of the SPD ensuring a connections are tighten to 3.6Nm
Type 2 Surge Protection Kit for Hager Consumer Units to aid compliance with 18th Edition BS 7671.
- Combination of high capacity voltage limiting varistors and N-PE spark gap
- Suitable for CT2 connection as per 534.4.3.2 BS7671 18th Edition
- Optical status indication for each cartridge Clear = Healthy, Red = Replace
- Pluggable surge protection modules for ease of replacement
- Each cartridge incorporates its own thermal disconnect mechanism
- Cartridges are mechanically coded to prevent mis-connection
- Cartridges can be routinely checked and changed if required without interrupting supply to loads
- No secondary back-up protection required.
Features:
- Power Supply System -TN / TT
- Requirement class -SPD class II acc. to IEC 61643-11; SPD Type 2 acc. to EN 61643-11
- Max. continuous operating voltage Uc -L-N: 275 V a.c. / N-PE: 260 V a.c.
- Nominal voltage Un -230/400 V AC 50/60 Hz
- Nominal discharge current In (8/20) microseconds 20 kA
- Max. discharge current I max (8/20) microseconds 40 kA
Data Sheet:
Click Here for Data SheetInstruction Manual:
Click Here for Instruction Manual